Concord

Electronic Overload Relays

1.COCR 3DE/3EZ

Features

In Built Protections

Specifications

Set Up Instructions

Wiring Diagram For EOCR 3EZ

Wiring Diagram For EOCR 3DE

2.EOCR DS

Features

Protection Functions

Specifications

Current Setting Type Range
05 0.5-6A
30 3-30A
60 5-60A
100A and above With External CT
Time Setting Start (D-Time) 0.2-30 sec
Trip (O-Time) 0.2-10 sec
Control Voltage 220 24-240VAC/DC
Contact Rating Mode 1SPDT (1C)
Rating 3A 250VAC
Status Normally Energized
Time current Characteristic Definite
Operating (Trip Indication) 2 LED with Fault Diagnosis
Mounting 35mm DIN Rail/Base

Example Wiring Diagram

Time Trip Characteristic – Definite (Inverse available on Request)

Time Trip Characteristic – Definite (Inverse available on Request)

Current Multiples of Current Setting

Overall Dimensions

3.EOCR SS – SOLID STATE PROTECTION RELAY ANALOG TYPE

Features

Protection Functions

Specifications

Current Setting Type Range
05 0.5-6A
30 3-30A
60 5-60A
100A and above With External CT
Time Setting Start (D-Time) 0.2-30 sec
Trip (O-Time) 0.2-10 sec
Control Voltage 220 24-240V AC/DC
Contact Rating Mode 2SPST 3A/250VAC
Rating 3A 250VAC
Contact Fail Safe / Non Fail Safe User selectable
Time current Characteristic Definite
Operating (Trip Indication) 2 LED
Mounting 35mm DIN Rail/Base

Protection Functions

Protected Items Operation Time
Over Current O-TIME
Phase Loss O-TIME
Locked Rotor O-TIME + D-TIME

Operation Display

“N” (Fail safe) Type converts95-96 to open and 95-98 to close when operating power is supplied to A1 and A2 (or L1 and L2).

Overall Dimensions

4.EOCR SSD – SOLID STATE PROTECTION RELAY ANALOG TYPE WITH DIGITAL DIPLAY

Features

Specifications

Current Setting
Type Range
05 0.5-6A
30 3-30A
60 10-60A
Starting Delay Time
(D-Time)
1-30 sec
Operating Time
(O-Time)
1-10 sec
Reset Manual/Remote
Overcurrent Trip Definite
Control Voltage 24~240V AC/DC
Contact Rating 2 SPST 3A/250VAC
Fault Diagnosis 7 segment LED Display
Mounting 35mm DIN Rail/Base

Protection Functions

Protection Function Operation Time
Over Current Operates after O-Time
Phase Loss Operates within 3 sec
Locked Rotor Immediately operates if 200% or more of the set current continues after D-Time

Trip Cause Method and Check Method

Product DImensions